Water in the Data Center: The Cost of Cooling

IT Sustainability · 4 min

Articles by Luís Carvalho

Water is now part of the European sustainability indicators for data centers. Learn how to interpret WUE, compare cooling solutions and assess colocation providers.

Water in the Data Center: The Cost of Cooling

TL;DR

Water has entered data center metrics

For years, data center efficiency was assessed mainly through energy consumption and indicators such as PUE (Power Usage Effectiveness). The European framework now includes a broader assessment of the resources used. Article 12 of Directive (EU) 2023/1791 on energy efficiency establishes reporting obligations for data centers covered by the scheme. Delegated Regulation (EU) 2024/1364 specified the indicators and methodologies for reporting to the European database, including information on water. In general terms, the scheme covers data center operators with an installed IT power demand of at least 500 kW, without prejudice to the exceptions and national rules that apply. For those who manage infrastructure or procure hosting services, this development reinforces the importance of assessing water consumption alongside energy, availability and operating costs.

The regulation requires measurement, not a specific technology

Delegated Regulation (EU) 2024/1364 defines water indicators that covered operators must report, including the total water input within the data center perimeter and the share coming from potable sources. WUE (Water Usage Effectiveness) is calculated by dividing the annual volume of water entering the facility, in cubic meters, by the energy consumed by IT equipment, in MWh. The methodology refers to standard EN 50600-4-9, giving preference to category 2 and allowing category 1 under the conditions provided for. It is important to distinguish water input from its actual consumption through evaporation: they are not necessarily the same quantity. The regulation sets out measurement and reporting rules, but does not require operators to adopt a specific cooling technology. In September 2026, the European Commission also adopted delegated act C(2026)3472, which provides for a common rating system with labels based, among other indicators, on PUE and WUE. Its application should be monitored in line with its entry into force and the regulatory timeline.

Less water can mean more energy

The choice of cooling technology affects both water and energy consumption. Under certain climate conditions, evaporative systems can reduce the energy required for heat rejection, although they use water during operation. Dry cooling solutions can significantly reduce that water requirement, but may demand higher electricity consumption during periods of high outdoor temperatures. Liquid cooling close to IT components also deserves a distinction: liquid circulating in a closed loop does not necessarily mean continuous water consumption, and the way heat is subsequently rejected to the outside is a decisive factor. It is therefore not enough to compare technologies by name or by an isolated efficiency figure. PUE and WUE should be analyzed together, taking into account climate conditions, load profiles, water availability and redundancy requirements. A solution that is efficient in one location may not perform the same way in another.

Water data should also be requested from the provider

Many organizations do not operate their own data centers, relying on colocation providers to host critical equipment and services. Although regulatory reporting obligations fall on the covered operators, customers can incorporate water indicators into their provider assessments. Where available, it is worth requesting the annual WUE, the volumes of water used, the source of supply, the measurement methodology and the proportion of estimated values. It is equally relevant to understand the measures planned for periods of extreme heat, water restrictions or supply failures, including any impacts on cooling capacity and operational continuity. These elements help assess the risk associated with the infrastructure and can support internal sustainability processes, where applicable. Comparisons between providers should consider the measurement perimeter, the reference period and the operating conditions, avoiding conclusions based on a single isolated indicator.

The metric has limits worth knowing

WUE is useful for tracking a data center's water usage, but on its own it does not represent its water impact. The same volume of water can have very different consequences in a region with high water availability or in an area subject to drought and supply restrictions. It is also important to distinguish potable water from other sources, as well as the water that enters the facility from the water that is actually consumed or returned to the environment. In addition, the WUE methodology used in European reporting does not directly incorporate all the water associated with generating the electricity consumed. Comparisons between facilities therefore require attention to climate, IT load, measurement perimeter and the origin of resources. Even for data centers below the mandatory reporting threshold, monitoring consumption and assessing cooling options can support investment decisions and operational management.

Balancing water, energy and resilience

The inclusion of water in European indicators reinforces the need to assess data centers beyond energy efficiency. There is no ideal cooling solution for every facility: the choice depends on climate conditions, technical architecture, water availability and source, operating costs and continuity requirements. For IT leaders, the most useful approach is to analyze PUE, WUE, supply risks and the ability to respond to extreme conditions together. When selecting providers, this information should complement the usual criteria of redundancy, availability and security. The goal is not to reduce water consumption at any cost, but to identify technically sustainable solutions that suit the local context and can preserve service resilience. Measuring correctly is the first step toward making better decisions.